On 30 September 2026, amendments to Approved Document B (Fire Safety) took effect in England. The headline change is simple: new blocks of flats with a top storey of 18 metres or more should have more than one common staircase. The update also sets out how to design buildings to support evacuation lifts where they’re provided, and includes transitional arrangements for projects already in the system.
The reason behind it is just as simple. For residents, the stairs are the way out. For firefighters, they’re the way in. In a building with a single staircase, one smoke-filled stairwell puts both at risk at the same time. If you design, build, manage or maintain tall residential buildings, these changes affect you.
Please note: This article summarises the changes for general information. It isn’t technical or legal advice. If the changes could affect a project, specification, tender, quote or advice you’re giving a client, check the requirements against the current official legislation and guidance, and confirm with your fire engineer and building control body how they apply to that specific project before you act.
Approved Document B is the government’s statutory guidance on meeting the fire safety requirements of the Building Regulations 2010 in England. It comes in two volumes:
It sets out what, in ordinary circumstances, may be accepted as one way to comply. You can take a different approach, but you’ll need to show it meets the regulations and agree it with your building control body early. For higher-risk buildings, that’s the Building Safety Regulator.
The government first published these amendments in March 2024 and reissued them in September 2024. They came out of a consultation that ran from December 2022 to March 2023. GOV.UK now hosts updated versions of both volumes with the 2026 changes built in.
The amended Volume 1 says flats should be served by more than one common stair if either of these applies:
The guidance now states that a single common stair arrangement is only suitable for buildings with a top storey under 18m.
Approved Document B measures the height of the top storey from the upper floor surface of the top floor to ground level on the lowest side of the building (Diagram D6). Roof-top plant areas, and any top storeys made up only of plant rooms, don’t count.
Start with what it doesn’t say: the amendments don’t make evacuation lifts mandatory. They set out how to design the building where evacuation lifts are provided. An evacuation lift is a lift that may be used to evacuate people in a fire. It matters most to residents who can’t use the stairs, so the guidance aims to give the lift the same protection as the stair beside it. Where a building has evacuation lifts:
Both volumes also gain new definitions for evacuation lift lobby, evacuation shaft and interlocked stair, plus an updated definition of storey exit that now includes a doorway giving direct access into an evacuation lift lobby within an evacuation shaft. In Volume 2, these definitions are the only changes.
Not necessarily. Transitional arrangements let some projects carry on under the previous edition (the 2019 edition incorporating the 2020, 2022 and 2025 amendments). A project qualifies only if both of these are true:
“Sufficiently progressed” has a set meaning:
If a project doesn’t meet both conditions, the amended guidance applies. The 18-month window closes in late March 2028, so schemes submitted in time that haven’t yet reached foundations or piling should check where they stand now.
Approved Document B guides building work. These changes don’t ask owners of existing blocks to retrofit a second staircase. But work to an existing building, and a material change of use (such as converting offices into flats), both count as building work, so the new guidance can apply to them.
More staircases and evacuation shafts mean more protected shafts, more fire-resisting construction and more fire doorsets, and every one of them only works if it’s built exactly as designed. That means compartmentation that holds, fire stopping that seals every service penetration, and smoke control that now has to protect the evacuation lift and lobby as well as the stair.
That’s the work we do. We install and remediate passive fire protection, including fire stopping and compartmentation, on residential buildings nationwide, and we deliver active systems such as automatic opening vents and disabled refuge communication alongside it. We’re FIRAS accredited, and we record every installation through Onetrace, so you can show exactly what went in, where and how, and drop that evidence straight into the building’s golden thread.
If you’re designing or delivering a residential building of 18m or more, talk to us early about the passive fire protection and smoke control the new layout needs.
Always check the current version on GOV.UK before acting on any of this.
On 30 September 2026, for use in England. Projects that meet the transitional arrangements can still follow the previous edition.
Not all. Under the amended guidance, blocks of flats with a top storey of 18m or more should have more than one common stair. Below 18m, a single stair can still be acceptable where each storey meets the criteria for a single escape route, or the building qualifies as a small single stair building.
From the upper floor surface of the top floor to ground level on the lowest side of the building. Roof-top plant areas, and top storeys that are only plant rooms, don’t count.
No. The guidance sets out how to design and protect evacuation lifts where a building has them: inside an evacuation shaft, with a protected lobby and the same level of protection as the stair.
No. Interlocked stairs, also known as scissor or stacked stairs, count as a single escape route, not an alternative means of escape.
It depends on progress on site. You can stay on the previous edition only if the work was sufficiently progressed before 30 September 2026, or is sufficiently progressed within 18 months beginning on that date. For a new building, that means pouring foundation concrete or permanent piling has started.
No. The amendments are for use in England. Wales, Scotland and Northern Ireland each set their own building regulations and guidance.
Join over 1,000 UK businesses who have already had Fire Protection installed by Ark Fire Protection.